Delta DVP — 3.4 Sequential Delay Output (Starting 3 Motors Sequentially)

3 . Timer Design Examples 3.4 Sequential Delay Output (Starting 3 Motors Sequentially) Oil Pump Motor Y0 START X0 STOP X1 Main motor Y1 Auxiliary Motor Y2 Control Purpose: z Starting the oil pump motor immediately when START is pressed. The main motor will be started after a 10 sec delay and then the auxiliary motor after a 5 sec delay. In addition, stopping all motors immediately when STOP is pressed. X0 X1 Y0 10s Y1 5s Devices: Y2 DVP-PLC Application Examples 3-4 Device Function X0 X0 = ON when START is pressed. X1 X1 = ON when STOP is pressed. T0 10 sec timer. Time base: 100ms T1 5 sec timer. Time base:

100ms Y0 Starting the oil pump motor Y1 Starting the main motor Y2 Starting the auxiliary motor