Delta DVP — 3.6 Artificial Fishpond Water Level Monitoring System (Flashing Circuit)

3. Timer Design Examples 3.6 Artificial Fishpond Water Level Monitoring System (Flashing Circuit) X2 X3 Y0 Y3 Y4 X1 Y1 X4 RESET X0 Y2 Control Purpose: z Feeding or draining water automatically when the water level of artificial fishpond is not at the normal level. In addition to feeding / draining water, enabling the alarm and alarm lamp when the water is above or below the alarm level. z Stopping the alarm when RESET is pressed. X0 500ms Y3/Y4 Alarm Alarm Lamp 500ms Devices: DVP-PLC Application Examples 3-7 4 Device Function X0 X0 = ON when the water is above the lowest level of alarm level. X1 X1 = ON when the water is above the lowest level of normal level.

X2 X2 = ON when the water is above the highest level of normal level. X3 X3 = ON when the water is above the highest level of alarm level. X4 X4 = ON when RESET is pressed. T1 500ms timer. Time base: 100ms. T2 500ms timer. Time base: 100ms. Y0 1# drainage pump Y1 Feeding pump Y2 2# drainage pump Y3 Alarm lamp Y4 Alarm