2 Functions of Devices in DVP-PLC b) When M1115 = On, the acceleration/deceleration pulse output will start. c) M1116 = On in the acceleration process. When the speed reaches its target, M1117 will be On. M1118 = On in the deceleration process. When the speed reaches its target, M1119 will be On. d) M1115 will not be reset automatically. You have to check the conditions during the process and reset it. e) Pulse output curves: Frequency (Hz) 10K 1K Number of pulses 10,000 70,000 80,000 Frequency (Hz) 10K 1K 2,606 8,606 11,213 Time (ms) Function Special High-Speed Puls Group e Output Number M1133 ~ M1135, D1133 Contents: 1.
Special D and special M for special high-speed pulse Y0 (50kHz) for SA/SX/SC: (The special data registers an d the special auxiliary relays are not applicable to SC V1.4 and above. They are not applicable to SX V3.0 and abov cause the function is replaced by PLSY, which ed to output 50KHz bandwidth.) e be can be us 2. Par 133: ameters for D1 DVP-PLC Application Manual 2-93 No. Function M1133 Output switch for special high-speed pulse Y0 (50kHz) (On = enabled) M1134 On = Continuous output switch for special high-speed pulse Y0 (50kHz) M1135 “Number of pulses reached” flag for special high-speed pulse Y0 (50kHz) D1133 Start No.
of control register (D) for special high-speed pulse Y0 (50kHz) Index Function + 0 The lower 16 bits of the 32 bits for output frequency of special high-speed pulse Y0 + 1 The higher 16 bits of the 32 bits for output frequency of special high-speed pulse Y0 + 2 The lower 16 bits of the 32 bits for number of output pulses of special high-speed pulse Y0 + 3 The higher 16 bits of the 32 bits for number of output pulses of special high-speed pulse Y0