Mitsubishi — Chapter 6 Application Instructions API 00-49

6 Application Instructions API 00-49 API 16 Operands: S : Source of data D : Destination of data n : Number of data to be moved Explanations: 1. If S is used in device F, only 16-bit instruction is applicable. 2. Range of n : 1~ 512 (16-bit, 32-bit instructions) 3. See the specifications of each model for their range of use. 4. The contents in n registers starting from the device designated by S will be moved to n registers starting from the device designated by D . If n exceeds the actual number of available source devices, only the devices that fall within the valid range will be used. 5. ES/EX/SS do not support the use of KnX, KnY, KnM, KnS and E, F index register modification.

Program Example: When X10 = On, K10 will be moved to the 5 consecutive registers starting from D10. X10 FMOV K10 D10 K10 K10 D11 K10 D12 n=5 K10 D13 K10 D14 DVP-PLC Application Manual 6-29 Mnemonic Operands Function D FMOV P Fill Move Type OP Bit Devices Word Devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F FMOV, FMOVP: 7 steps DFMOV, DFMOVP: 13 steps S * * * * * * * * * * * D * * * * * * n * * PULSE 16-bit 32-bit EH3 SV2 ES EH3 EH3 ES EX SS SA SX SC EH SV EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV SV2 SV2 K10 D10 K5