6 Application Instructions API 00-49 M1000 M1049 Y0 X2 Y1 X3 X0 Y0 X2 Y0 X1 Y1 X3 Y1 M1048 Y2 X4 ANRP (1) M1048 and D1049 are valid only when M1049 = On. (2) When Y0 = On for more than 10 seconds and the device fails to reach the frong position X2, S910= On. (3) When Y1 = On for more than 10 seconds and the device fails to reach the back position X3, S920= On. (4) When backward switch X1 = On and backward device Y1 = On, Y1 will go Off only when the device reaches the back position switch X3. (5) Y2 will be On when any annunciator is enabled. Whenever X4 is on, 1 annunciator in action will be reset. The reset starts from the annunciator with the smallest No.
DVP-PLC Application Manual 6-72 ANS T0 K100 S910 ANS T1 K200 S920