Mitsubishi — Chapter 7 Application Instructions API 50-88

7 Application Instructions API 50-99 Remarks: 1. The output contact of the high speed counter and the comparative outputs of API 53 DHSCS, API 34 DHSCR and API 55 DHSZ instructions only perform comparison and contact outputs when there is a counting input. When using data operation instructions, e.g. DADD, DMOV, for changing the present value in the high speed counter or making the present value equals the set value, there will not be comparisons or comparative outputs because there is no counting inputs. 2. High speed counters supported by ES/EX/SS series MPU (total bandwidth: 20kHz): U: Progressively increasing input A: A phase input S: Input started D: Progressively decreasing input B:

B phase input R: Input cleared a) Input points X0 and X1 can be planned as counters of higher speed (1 phase input can reach 20kHz). However, the total counting frequency of the two input points has to be smaller or equal 20kHz. Provided the input is a 2-phas input signal, the counting frequency will be approximately 4kHz. The frequency of the input points X2 and X3 (1-phase) can reach 10kHz. b) For ES/EX/SS series MPU, the uses of DHSCS instructio with DHSCR instruction cannot be more than 4 times. 3. High speed counters supported by SA/SX series MPU (total bandwidth: 40kHz): U: Progressively increasing input A: A phase input S: Input started D: Progressively decreasing input B:

B phase input R: Input cleared a) Input points X0 and X1 for 1-phase input can reach a frequency of 20kHz and X2 ~ X5 can reach 10kHz. 2-phase input (X0, X1) C251, C252 and C254 can reach a frequency of 4kHz and C253 reach 4kHz (only b) Functions of the input point X5: supports 4 times frequency counting). i) When M1260 = Off, C240 is the general U/D high speed counuter.

DVP-PLC APPLICATION MANUAL 7-7 Type 1-phase 1 input 1-phase 2 inputs 2-phase 2 inputs C235 C236 C237 C238 C241 C242 C244 C246 C247 C249 C251 C252 C254 Input X0 U/D U/D U/D U U U A A A X1 U/D R R D D D B B B X2 U/D U/D R R R R X3 U/D R S S S Type 1-phase 1 input 1-phase 2 inputs 2-phase 2 inputs C235 C236 C237 C238 C239 C240 C241 C242 C244 C246 C247 C249 C251 C252 C253 C254 Input X0 U/D U/D U/D U U U A A B A X1 U/D R R D D D B B A B X2 U/D U/D R R R R X3 U/D R S S S X4 U/D X5 U/D