10 Application Instructions API 202-313 Operands: D : Destination output device n : Device specifying the output bit Explanations: 1. EH2/SV_V1.9 and versions above, and EH3/SV2 supports the function. EH series does not support the dunction. 2. Available range for the value in operand n : K0~K15 for 16-bit instruction; K0~K31 for 32-bit instruction. 3. BOUT instruction performs bit output on the output device according to the value specified by operand n. Status of Coils and Associated Contacts: Program Example: Instruction: Operation: LDI X0 Load NC contact X0 AND X1 Connect NO contact X1 in series.
BOUT K4Y0 D0 When D0 = k1, executes output on Y1 When D0 = k2, executes output on Y2 DVP-PLC Application Manual 10-21 API Mnemonic Operands Function 266 D BOUT Output Specified Bit of a Word Type OP Bit Devices Word devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F BOUT: 5 steps DBOUT: 9 steps D * * * * * * n * * * * * * * * * * * PULSE 16-bit 32-bit SA SX SC EH SV EH3 SV2 ES EX SS SA SX SC EH3 ES EX SS SA SX SC EH3 ES EX SS EH SV EH SV SV2 SV2 BOUT instruction Evaluation result Associated Contacts Coil NO contact (normally open) NC contact (normally closed) FALSE OFF Current blocked Current flows TRUE ON Current flows Current blocked BOUT K4Y0 D0