Delta — 1.5 Wiring Diagram

DVP02TK-S/DVP02TU-S Temperature Control Module Manual  Mounting Arrangements and Wiring Notes How to install DIN rail DVP-PLC can be secured to a cabinet by using the DIN rail of 35mm in height and 7.5mm in depth. When mounting PLC to DIN rail, be sure to use the end bracket to stop any side-to-side movement of PLC and reduce the chance of wires being _1 loosen. A small retaining clip is at the bottom of PLC. To secure PLC to DIN rail, place the clip onto the rail and gently push it up. To remove it, pull the retaining clip down and gently remove PLC from DIN rail, as shown in the figure.

Please install PLC in an enclosure with sufficient space around it to allow heat dissipation as shown in the figure. D D DVP MP D D Warning: shock hazard. Only for mounting in a rack or enclosure fully enclosing all live parts. D > 50 mm Avertissement : risque d’йlectrocution. Ne doit ktre installй que dans un bвti ou un bootier recouvrant entiиrement toutes les piиces sous tension. 1.5 Wiring Diagram 22-16AWG 1. Use 22-16AWG (1.5mm) single or multiple core wire on I/O wiring terminals. The specification of the terminal is shown in the figure above. The PLC terminal screws shall be tightened to 1.95 kg-cm (1.7 in-lbs). 2.

DO NOT place the I/O signal wires and power supply wire in the same wiring duct. 3. Warning: use conductors with insulation rated for at least 75 °c Avertissement : employer des conducteurs pour au moins 75 °c. 4. For use with copper conductors only (excluding thermocouplers). destinй а ktre utilisй avec des conducteurs en cuivre seulement (sauf thermocouples). 1-10