Delta — 2.1.4 Basic Setup Page

DVP02TK-S/DVP02TU-S Temperature Control Module Manual _2 2-6 TU CR# TK CH1 TK CH2 Attribute Name Description Default Page0 Page10 Add. (Hex) Add. (Hex) K21: Cu50 K22: Cu100 K23: Ni100 K24: Ni1000 K25: LGNi1000 K26: 0~10V (Quick AI) K27: Ni120 #12 00C 0EC R/W O Unit of temperature K0: OC K1: OF K0 #13 00D 0ED R/W O Offset temperature error K-999 ~ K999 K0 #14 00E 0EE R/W O Temperature filter range Temperature filter ranging 10~10000 When the value inputted is in the range of ±10 of the last inputted value, the system will run the filtering measurement. Hence, when the noise interference is bigger, the filter range should set to bigger too. K10 #15 00F 0EF R/W O Filtering factor Ranging 0~50.

Operational formula: value = (last value*n + this measurement ) / (n+1) When the set value is less, the PV will be closer to this measurement. When the set value is bigger, the filtering factor will be bigger and the PV will be similar. K1 #16 010 0F0 R/W O Control type K0: PID Auto K1: PID Manual K2: PID program control K3: ON/OFF (for DVP02TUR-S/DVP02TUN-S/ DVP02TKR-S/DVP02TKN-S) K0 #17 011 0F1 R/W O Output 1 control K0: Heating K1: Cooling K2: Alarm (for DVP02TUR-S /DVP02TUN-S/ DVP02TKR-S /DVP02TKN-S) K3: Proportion (for DVP02TUL-S/ DVP02TKL-S) K0