EVADA · 11 стр.
E48300 User Manual (EN)
Оригинальное название: E48300 User Manual
Похожие инструкции
Текст документа
技术规格书 高性能、高可靠性电源产品 版本号: V1.0 E48300-8U300Aembedded power supply Table of contents 1. Overview 3 2. The main specifications of the product 3 3. Reference standards and specifications 3 4. Principle introduction 4 6. Electrical characteristics 5 1. Input characteristics 5 2. Output characteristics 6 3. Protection characteristics 7 7. Other requirements 6 8. Safety regulations, lightning protection and EMC characteristics 6 Nine. Precautions 8 10. Mechanical properties 8 11. Reliability requirements 8 12. Packaging, Storage and Transportation Requirements 8 Attachment: Layout Drawing 9 第 1 页 共 11 页
技术规格书 高性能、高可靠性电源产品 版本号: V1.0 E48300-8U300Aembedded power supply I. Overview E48300-8U300A embedded power supply is a new generation of highly reliable and high-performance communication power supply system designed by the company based on years of experience in development and online operation. The system configuration supports 1-6 hot-swappable rectifier modules. The system monitoring module has the function of battery management and power system monitoring. It can realize environmental monitoring by configuring appropriate sensors, and provide multiple groups of backup monitoring data.
It can also provide RS485 communication interface, which is convenient for remote monitoring and unattended. This embedded power supply is mainly used in outdoor cabinets. 2. The main specifications of the product 3.
Reference standards and specifications (1) YD/T 1058-2015 "High Frequency Switching Power Supply System for Communication" (2) YD/T 731-2018 "High Frequency Switching Rectifier for Communication" (3) YD/T 585-2010 "Power Distribution Equipment for Communications" (4) YD/T 1051-2010 "General Technical Requirements for Communication Bureau (Station) Power System" (5) YD/T 5040-2005 "Code for Design of Communication Power Equipment Installation Engineering" (6) YD/T 983-2013 "Electromagnetic Compatibility Limits and Measurement Methods for Communication Power Supply Equipment" (7) YD/T 944-2007 "Technical Requirements and Test Methods for Lightning Protection of 第 2 页 共 11 页 Output maximum power Input voltage range The output voltage Output maximum current Rectifiers 18KW 90-300Vac 53.5V 300A RM4850*6(Fully equipped 6PCS) 配置 Input branch:
63A/4P*2+mechanical interlock Output branch: 16A/1P*5, 10A/1P*3, five-hole maintenance socket*1 Battery access: 125A/1P*4 Power off at one time: users 1-3-125A/1P*2, 32A/1P*1; user 4-63A/1P*2 Second power off: users one to four: 32A/1P*1, 100A*4 normally closed DC contactor for electricity under load 200A normally closed DC contactor for battery power off Specific configuration: can be customized according to customers Accessories Class C lightning protection: AC-SPD and DC-SPD
技术规格书 高性能、高可靠性电源产品 版本号: V1.0 E48300-8U300Aembedded power supply Communication Power Supply Equipment" (8) YD 5083-2005 "Code for Testing Seismic Performance of Telecommunications Equipment" (9) YD 5096-2005 "Code for Seismic Performance Testing of Communication Power Supply Equipment" (10) QZTT 1007-2014 "Summary of Standards for New Supporting Facilities of China Tower Co., Ltd." (11) QZTT ****-2015 "Embedded High Frequency Switching Power Supply System Monitoring Specification (Trial) 4. Principle introduction The principle of IPS30000-8U300A embedded power supply system is shown as follows:
The power supply of the system is switched between the mains and the oil generator through the AC input circuit breaker to supply power to the rectifier module; at the same time, L1, L2, L3, and N are sampled and processed and then sent to the monitoring signal interface for AC voltage detection.After the output of the rectifier 第 3 页 共 11 页
技术规格书 高性能、高可靠性电源产品 版本号: V1.0 E48300-8U300Aembedded power supply 第 4 页 共 11 页 module is concatenated, the positive pole is directly connected to the positive pole of the load and the battery, and the negative pole is divided into 9 routes. The first route is output to the secondary load DC input terminal through the user's first shunt and the primary power-off DC contactor.
The second route Output to the important load DC input terminal through the first user shunt, the third output to the secondary load DC input terminal through the second user shunt and the primary power-down DC contactor, and the fourth output to the important load DC through the second user shunt Input terminal, the 5th channel outputs to the secondary load DC input terminal through the user-shunt and the primary power-down DC contactor, the 6th channel outputs to the important load DC input terminal through the user-1 shunt, and the 7th channel passes through the user-shunt output to the DC input terminal of the secondary load, the 8th channel outputs to the DC input terminal of the important load through the user-shunt, the 9th channel passes through the shunt and the DC contactor to the negative pole of the battery input, all DC The contactor realizes battery over-discharge protection for the battery under the control of monitoring.
All shunts send signals to the monitoring board, and the monitoring board calculates and processes the current collected from user 1 to user 4, and at the same time performs metering as required and sends it out through the display screen. 5. Environmental conditions Environmental parameters Environmental conditions of use environmental conditions of transport Environm ental conditions for storage Remark Project Parameter Unit Clim atic condi tions tempe rature low temperature ℃ -40 -40 -45 It can start at full load at -40°C, and linearly derate 20% at +55~+65°C high temperature ℃ 55 70 70 humid ity low relative humidity % 5 / 5 / high relative humidity % 95 / 95