SINUS PENTA ИНСТРУКЦИИ ПО ПРОГРАММИРОВАНИЮ 425/ 426 Пользова- Пользова- Параметр по умолчанию Параметр по умолчанию тельское тельское C21x Braking Unit C210-Enab/Vel [*] BrakeO C211-BrakeTon 2.00 s C212-BrkDutyCycle 10 % C21x-C22x DC Braking C215-Enab dcb stop 0: No C216-Enab dcb start 0: No C217-Tdcb stop 0.5 s C218-Tdcb start 0.5 s C219-dcb speed 50 rpm C220-I dcb 100 % C221-I dcb hold 0 % C222-Tdefl M1 [*] C223-Tdefl M2 [*] C224-Tdefl M3 [*] C22x-C23x Mains Loss C225-pwd type 3: Alarm C226-Tpdd 10 ms C227-Tpddec 20 s C228-Pddecboost 0.10 % C229-Pddcder 1 C230-Vpddel [**] C231-Kpvdclc 0.050 C232-Kivdclc 0.500s C234-stopmode 0:
Stop C235-stoplev 0 rpm C24x Speed Searching C245-Enab SpdSch 0: No C246-tssd 1 s C247-SpsRate 10 % C248-Is 75 % C249-SpsSpd 0: Last Speed C25x AutoReset C255-nPulsRes Disable C256-T ResCyc 300 s C257-PowOnRes 0: No C258-UvMlStore 0: No C26x-C27x Thermal Protection C264-FanTemp 50 °C C265-ThermProt M1 0: No C266-ThermCurr M1 120 % C267-ThermConstM1 360s C268-ThermProt M2 0: No C269-ThermCurr M2 120 % C270-ThermConstM2 360s C271-ThermProt M3 0: No C272-ThermCurr M3 120 % C273-ThermConstM3 360s C274-PTC ThermProt 0:Disable C27x Maintenance C276-Set OP Time 0h C276-Set SP Time 0h C28x-C29x PID Configuration C285-Sel InPID 1 2: AIN1 C286-Sel InPID 2 0: Disabled C287-Sel InPID 3 0:
Disabled C288-Sel Fdbk 1 PID 3: AIN2/PTC C289-Sel Fdbk 2 PID 0: Disable C290-Sel Fdbk 3 PID 0: Disable C291-PID Mode 0: Disable C291a-PID Control 0: Standard SUM mode C291b-PID Mode 0: Disable C292-Der Mode 0: Measure C293-PID Struct 0: No C294-PID Act 1: Reference C30x Crane C300-StartTrq ref.pos. 0.0 % C301-t StartTrq ref.pos. 0 ms _ C300a-StartTrq 0.0 % ref.neg. C301a-t StartTrq _ 0 ms ref.neg. C302-Brk On 0: None _