E774GB — 6.5.2 Lead fuses

KUHNKE Automation 6.5 Output 6.5.1 Branch Circuit protection according UL 508A UL 508A specifies how output wires for use are to be protected. Compliance with the following points is mandatory. • Every PHC output wire shall be protected (UL 508 31.2.1) because it is energized towards the ground potential. • Fuses shall be easily accessible and replaceable at no risk for the operator (UL 31.2.3). • Use only UL Class CC fuses with a voltage of 600VAC and a break- ing capacity of 200 kArms. • The maximum fuse value of each channel is 12 A. 6.5.2 Lead fuses The standard demands the use of Class CC fuses at a rated voltage of 600 VAC and a rated interruption capacity of 200 kA rms .

Fuses shall be UL listed. Example fuse: KLKR015 Class CC Fuse. Branch Circuit Protection Load Wiring diagram with additional Branch Circuit protection for CH1 and CH2 E 774 GB 29 30.06.2014