sinee — EM303B User Manual (EN)

User Manual EM303B General Purpose Inverter EM303B provides 2 programmable analog output terminals: M0 and M1 which can output 0 ~ 10V voltage signal or 0-20mA current signal by jump line selection. See Table 7-4 for analog outputs full scales and the description of F2-16~F2-27. Remarks: 102 No. Function Description 18 Overvoltage Stall If overvoltage stall occurs, the output terminal is on. 19 Current Limit If overcurrent stall occurs, the output terminal is on. Frequency Zero Speed Detection(Output Frequency Detection) When inverter is running, if the output frequency ≤ the setting value of F9-09, inverter will be considered as running at zero speed, the output terminal is on.

20 21 Not Used Motor 2 Enabled When motor 2 is selected as enabled (Motor is switched by multi-function numeric input terminal), the output terminal is on. 22 Setting running time is up When the setting running time of Fd-27 is up, the output terminal is on. 23 24 Not Used 25 Not Used Inverter is ready for running When inverter is power-on normally and no fault occurs, the output terminal is on. 26 27 Not Used FDT1 lower bounds(pulse) When output frequency falls below the setting value of FDT1 lower bounds, the corresponding terminal will output a pulse whose width is determined by the parameters set up in FE group.

28 FDT2 lower bounds(pulse) When output frequency falls below the setting value of FDT2 lower bounds, the corresponding terminal will output a pulse whose width is determined by the parameters set up in FE group. 29 FDT1 lower bounds(void when JOG, pulse) When output frequency falls below the setting value of FDT1 lower bounds, the corresponding terminal will output a pulse whose width is determined by the parameters set up in FE group. No pulse output in JOG state. 30 FDT2 lower bounds(void when JOG, pulse) When output frequency falls below the setting value of FDT2 lower bounds, the corresponding terminal will output a pulse whose width is determined by the parameters set up in FE group.

No pulse output in JOG state. 31 ILP Fault When inverter trips the fault of input phase loss, the output terminal is on. 32 No. Function Range Unit Default Type F2-16 Analog Output Terminal M0 See Table 7-4 Analog Output Full Scale % 0 〇 F2-17 Analog Output Terminal M1 % 6 〇