sinee — EM303B User Manual (EN)

User Manual EM303B General Purpose Inverter On special occasions, user can set a bias curve of analog signal. Ones place: VS voltage bias options F8-01 ones place=0/1/2 corresponding to input / output bias 0/1/2 Tens place: VF voltage bias options F8-01 tens place=0/1/2 corresponding to input / output bias 0/1/2 Hundreds place: IS current bias options F8-01 hundreds place=0/1/2 corresponding to input / output bias 0/1/2 Thousands place:

IF current bias options F8-01 thousands place=0/1/2 corresponding to input / output bias 0/1/2 VP Bias Options F8-02 ones place=0/1/2 corresponding to input / output bias 0/1/2 8.10.4 Setting Bias Curve of Analog Setting Signal F8-08 ~ F8-15 set input/output bias 0. F8-08, F8-09, F8-10, and F8-11 set the output bias of 4 points of user defined bias curve. They can be set continuously in the range of 0.0% ~ 100.0%. F8-12, F8-13, F8-14, and F8-15 set the analog inputs of 4 points of user defined bias curve. 135 Tens place:VF voltage bias options 0: Input / output bias 0 1: Input / output bias 1 2: Input / output bias 2 Hundreds place: IS current bias options 0: Input / output bias 0 1:

Input / output bias 1 2: Input / output bias 2 Thousands place: IF current bias options 0: Input / output bias 0 1: Input / output bias 1 2: Input / output bias 2 VP Bias Options 0: Input / output bias 0 1: Input / output bias 1 2: Input / output bias 2 2 〇 F8-02 No.

Function Range Unit Default Type F8-08 Output Bias 0 0 0.00~100.00 % 0.00 ● F8-09 _ Output Bias 0 1 0.00~100.00 % 25.00 ● F8-10 _ Output Bias 0 2 0.00~100.00 % 75.00 ● F8-11 _ Output Bias 0 3 0.00~100.00, 100.00=Fmax % 100.00 ● F8-12 _ Input Bias 0 0 0.00~ Input Bias 0 1 % 0.00 ● F8-13 _ Input Bias 0 1 _ Input Bias 0 0~ Input Bias 0 2 % 25.00 ● F8-14 _ Input Bias 0 2 _ _ Input Bias 0 1~ Input Bias 0 3 % 75.00 ● F8-15 _ Input Bias 0 3 _ _ Input Bias 0 2~100.00 % 100.00 ●