User Manual EM303B General Purpose Inverter See Figure 11-1 for the overall and installation dimensions of remote control case. 150 115.5 141 Run Stop 250 12.3 Braking Resistor Figure 11-1 Outlook and Installation Dimensions of Remote Control Case EM303B (0.75 ~ 15kW) with an integrated braking unit can be connected to braking resistor directly for quick stop. Please see Table 11-1 for selecting braking resistor for EM303B. Table 11-1 Braking Resistor Selection Remarks: 1. See User Manual of BR100 Braking Unit for selecting braking resistor for EM303B-018~400. 2. Cables listed in above table refer to the lead cable of single resistor.
The DC bus should be uprated if the resistors are in parallel connection. 3. Cable should withstand voltage≥AC450V, temperature resistance :105 ℃ . 4. Because there is a resistor limit of power consumption, the longest operation time for 10%ED is 10S (On: 10S/ Off:90S). 173 130 238 210 Output Frequ Run Emergency Sto Acceleration Deceleration Inverter Model No.
Motor Pow er MIN Resistor Resistance(Ω) Resistor power Cable Size (kW) (W) (mm2) EM303B-0R7G /1R1P -3B 0.75 ≥360 ≥112.5 1 EM303B-1R1G /1R5P -3B 1.1 ≥360 ≥165 1 EM303B-1R5G /2R2P -3B 1.5 ≥180 ≥225 1.5 EM303B-2R2G /3R0P -3B 2.2 ≥180 ≥330 1.5 EM303B-3R0G /4R0P -3B 3.0 ≥180 ≥450 1.5 EM303B-4R0G /5R5P -3B 4.0 ≥90 ≥600 2.5 EM303B-5R5G /7R5P -3B 5.5 ≥60 ≥825 4 EM303B-7R5G /9R0P -3B 7.5 ≥60 ≥1125 4 EM303B-9R0G /011P -3B 9.0 ≥60 ≥1350 4 EM303B-011G /015P -3B 11 ≥30 ≥1650 6 EM303B-015G /018P -3B 15 ≥30 ≥2250 6