User Manual EM303B General Purpose Inverter  Connect to PC or PLC through RS485/RS232 converter Figure 3-20 Wiring Communication Terminals Remarks: For the applications with severe electromagnetic noise, please ground the GND of communication points to the common ground. 3.3.9 Size of Control Circuit Cable and Screw To lower interference and attenuation of control signal, the cable length of control signal should be in a maximum of 50m, and the distance should be in a minimum 30cm between the signal cable and the power cable. Twisted-pair cable or shielded cable shall be used when inputting analog signal externally. It shall be the best to take 0.5~1mm2 cable as the control circuit cable.

There are two types of control circuit wiring terminals for EM303B: clamp terminal and barrier terminal, please install them with a PH0 cross head screwdriver with a tightening torque of 0.5N.m. Please pay attention to followings based on different features of these two terminals: Clamp terminal  Take pin terminal or cable strip length by 5~7mm for connection.  Only after the terminal screw is fully loosened anticlockwise first, the cable can be inserted. Barrier terminal  Take a circular or a U-sharp clamp terminal with holes of 3.5mm. 3.3.10 Precautions for Wiring Control Circuit 1. Separate the control circuit cable from the other cables. 2.

Separate the cable of control circuit terminals EA, EB, EC, Y1, and Y2 from the cables of other control circuit terminals. 3. Use shielded twisted-pair cables for control circuit to avoid malfunctions caused by interference. The wiring distance should be in a maximum of 50m. 4. Wrap the shield net with insulating tape to prevent the shield net from contacting with other signal cables and housing of device. 37 A+ EM303B A- GND PE 485+ 485- GND RS485/RS232 Converter 232+ 232- PC/PLC 232 Communication Terminals