User Manual EM303B General Purpose Inverter 5 Trial Operation 5.1 Trial Operation Procedures Table 5-1 Procedures of Trial Operation 49 Procedure Working Scope Check inverter’s rated power, and install the inverter as per the requirements stated in Chapter 2. Installation Wiring the Inverter Wiring as per the requirements stated in Chapter 3. 1. Be sure the input voltage of power supply matches the rated voltage of inverter. 2. The input power supply circuit connects to a breaker 3. The inverter is grounded. 4. Power supply cable is connected to input terminals R, S and T of the inverter correctly 5. Motor is connected to output terminals U, V, and W of the inverter correctly. 6.
Correct control circuit wiring. 7. External switch is at right status. 8. Motor is disconnected from the mechanical system when idling. Check Before Power-on 1. Check if there is unexpected noise, odd smell, or smoke with inverter. 2. When power is on, the keypad display is normal, no fault and alarming. 3. Turn off the power immediately if any emergency, and check as per the instruction in Chapter 9. Check at Power-on After the initial operation of inverter, maintenance or motor replaced, reset the parameters as defaults, and then conduct following operations. Parameter Setting Input Correct Motor Nameplate Input and confirm the parameters listed on motor nameplate.
Otherwise, serious damage may occur in operation. Parameter Set correct limit parameters, protection parameters and protection modes of inverter and motor, mainly as: maximum frequency, upper-limit frequency, lower-limit frequency, lower-limit frequency running time, fault retry control, relay fault output. Setting Protection Parameter of Motor and Inverter 1. Obtain correct motor parameters by autotuning motor parameter before the initial operation in selecting vector control mode. 2. Use stationary autotuning motor parameter if motor cannot disconnect the load. 3. Do not autotune motor parameters if the motor is running.
Autotuning Motor Parameter Set rotational direction, F/R control, acceleration/deceleration time, control mode, star/stop mode, and input mode directly based on driving system working conditions. General Setting Parameter Operation Set parameters of V/F curve scaling, torque boost, slip compensation, and AVR function based on load needs. Control V/F Control Parameter Set parameter of regulator and torque control, and setting parameters based on load conditions. Vector Control When motor is idling, start inverter in keypad or terminal control mode, check and confirm the running status of drive system. 1. Motor:
stable operation, normal rotation, correct rotational direction, normal acceleration/deceleration process, no unexpected vibration, noise or odd smell. 2. Inverter: correct data displayed on the control panel, fans and relays working Idling Trial Operation Check