User Manual EM303B General Purpose Inverter 73 3: IS* PID output 4: IF* PID output 5: Auxiliary frequency* PID output Frequency of Zero Speed Detection 0.00~50.00/0.0~50.0 Hz 0.00 〇 297 F9-09 No.
Function Range Unit Default Type S/N Zero Speed Detection Output Delay 0.00~600.00 S 1.00 〇 298 F9-10 Frequency Reach Range FAR 0.00~50.00/0.0~50.0 Hz 2.50 〇 299 F9-11 F9-12 FDT1 Increasing Threshold 0.00~Fmax /0.0~Fmax Hz 30.00 〇 300 FDT1 Decreasing Threshold 0.00~Fmax /0.0~Fmax Hz 30.00 〇 301 F9-13 F9-14 FDT2 Increasing Threshold 0.00~Fmax /0.0~Fmax Hz 30.00 〇 302 FDT2 Decreasing Threshold 0.00~Fmax /0.0~Fmax Hz 30.00 〇 303 F9-15 Cut-off Frequency of Oscillation Suppression 20~400 % 90 〇 304 F9-16 Non-Stop Control Options at Instantaneous Power Failure 0: Disabled 1:
Enabled 0 〇 305 F9-17 F9-18 Speed Search Current 0.30~1.50 0.60 〇 306 F9-19 Speed Search Coefficient 1.00~1.30 1.05 〇 307 Control Voltage of Non-Stop at Instantaneous Power Failure 0~800 V 537 ● 308 F9-20 Proportion Gain of Non-Stop at Instantaneous Power Failure 0.00~300.00 0.50 ● 309 F9-21 Integral Time of Non-Stop at Instantaneous Power Failure 0.00~600.00 S 1.50 ● 310 F9-22 Base Time ofNon-Stop at Instantaneous Power Failure 0.00~600.00 S 2.00 ● 311 F9-23 Start Delay Time After Power-on 0.00~10.00 (The time for inverter to wait for the initial operation after power-on) S 1.00 ● 312 F9-24 Terminal Operation Command Control 0: Terminal shall be off first, and then on. 1:
Terminal shall not be off, inverter will run directly. 1 〇 313 F9-25 Voltage Resume Time of Speed Search 0.00~5.00 S 0.30 ● 314 F9-26 F9-27 Oscillation Suppression 0~20000 300 ● 315