sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 145 start-stop way 1: Remote control F28.02 Loading way 0: Automatic 1: Manual 0 〇 F28.03 Loading Lower limit Frequency 0.00~Fup Hz 25.00 ● F28.04 Manual loading control command 0: reset 0 uninstall 1:To 1 Load 0 ● F28.05 Dormancy Delay 10~7200 s 1200 ● F28.06 Unloading operation frequency 0.00~Fup Hz 20.0 ● F28.07 Shutdown and restart delay time 1~300 s 60 ● F28.08 Shutdown delay time 0~60000 s 5 ● F28.09 Maximum pressure range 0.5~25.00 MPa 1.60 〇 F28.10 Pressure feedback selection 0: AI1 1: AI2 2: AI3 3: AI4 4:

HDI 0 〇 F28.11 Pressure Digital given 0.00~Upper Limit Pressure value MPa 0.80 ● F28.12 Early-warning pressure Pressure Digital given~ Warning pressure MPa 0.98 ● F28.13 Warning pressure Early-warning pressure~ Maximum pressure range MPa 1.00 ● F28.14 Pressure proportional gain GP 0.00~100.00 5.00 ● F28.15 Pressure integral time GTi 0.000~60.000, 0.000: No Integral s 10.000 ● F28.16 Pressure differential time GTd 0.000~60.000 ms 0.000 ● F28.17 Pressure integral action range 0.00~100.00 % 100.00 ● F28.18 Pressure Regulation Upper Limit 0.00~100.00 % 100.00 ● F28.19 Pressure regulation Lower Limit 0.00~100.00 % 25.00 ● F28.20 lower Limit 0.00~ Upper Limit pressure value MPa 0.75 ●