sinee — 7.3 F02 Group: Input Terminal Parameter

EM500 Open-Loop Vector Control Inverter User Manual the function codes F02.00 - F02.14, user can define the functions of those input terminals X1 - X11 and AI1 - AI4 are 15 numeric multi-function input terminals. By setting respectively. For example, if F02.00=1, X1 is “RUN”. If the terminal control (F00.02=1) is selected as the command source, then inverter starts the function RUN when X1 terminal input is valid. See Table 7–4 for specific function options. If more than one terminal is set to the same function (except the function 34), the function is determined by the state of two terminals or logic.

For example, If F02.00=1 and F02.05=1 ether X1 or X6 is effective “RUN” of inverter is effective. Table 7–4 Numeric Multi-Function Input Terminals 177 (Expansion Card) F02.12 X9 Numeric Input Function (Expansion Card) 0 〇 F02.13 X10 Numeric Input Function (Expansion Card) 0 〇 F02.14 X11Numeric Input Function (Expansion Card) 0 〇 Value Function Description 0 No Function Set “0: No Function” for an unused or fault terminal to prevent false output.

1 Run Terminal “RUN” If the terminal control (F00.02=1) is selected as the command source, inverter executes the function F/R according to the setting value of the terminal control mode F00.03 under the condition that the function terminal is enabled. (See F00.03 Function Code) 2 Direction R/F If the terminal control (F00.02=1) is selected as the command source, inverter executes the function F/R according to the setting value of the terminal control mode F00.03 under the condition that the function terminal is enabled.

(See F00.03 Function Code) 3 3-Wire Sequence Stop Control If the terminal control (F00.02=1) is selected as the command source and the terminal control mode is 3-wire sequence control (F00.03=2/3), inverter executes the stop command under the condition that the function terminal is enabled. (See F00.03 Function Code)