sinee — 7.23 F27 Winding rolling application

EM500 Open-Loop Vector Control Inverter User Manual 328 F09.07 Differential Time 1 30.000ms 30.000ms 30.000ms F09.08 Proportional Gain 2 0.10 0.40 0.07 F09.09 Integral Time 2 0.000s 0.000s 4.000s F09.10 Differential Time 2 30.000ms 30.000ms 50.000ms F09.11 PID Parameter Switching 2: Automatic Switching by Offset 2: Automatic Switching by Offset 2:

Automatic Switching by Offset F09.12 PID Parameter Switching Offset 1 5.00% 0.00% 5.00% F09.13 PID Parameter Switching Offset 2 45.00% 100.00% 45.00% F09.16 Upper Limit of PID Output 40.0% F09.17 Lower Limit of PID Output -50.0% -50.0% -40.0% F09.19 PID Differential Limit 1.00% 1.00% 0.50% F09.21 PID Setting Variation Time 2.000s 2.000s 0.500s F09.35 The Feedback Voltage Upper Limit 9.50V 9.50V 9.50V F09.36 The Feedback 0.50V 0.50V 0.50V