sinee — 9.3.4Excessively Long Deceleration Time

EM500 Open-Loop Vector Control Inverter User Manual  Coast-to-stop terminal FRS=ON: Switch FRS=OFF.  Control switch is disabled: Check control switch.  Motor can only run in one direction.  Setting reference input frequency= 0: Increase reference input frequency. Reverse prohibited: When F00.21=1, inverter reverse is prohibited.  Motor reverses The output phase sequence of inverter is not identical to that of motor input: When power is off, the running direction of motor can be changed by switching any of the two connection wires on the output side of inverter.

9.3.3Excessively Long Acceleration Time  Excessively low setting of current limit limit, then output frequency will remain unchanged in acceleration, and it will rise When current limit is enabled, if output current of inverter reaches its set current continuously only until output current is lower than the setting current limit. In this case, the acceleration time of motor is longer than the set time. Check if the set current limit of inverter is excessively low.  If the set acceleration time is too long, confirm its parameters. 9.3.4Excessively Long Deceleration Time  When energy consumption brake is enabled,  The brake resistance is too big.

The energy consumption brake power is too  The set value of brake duty ratio (F15.32) is too small, and the deceleration small, so the deceleration time is prolonged. time is prolonged. Please increase the set value of brake duty ratio.  If the set acceleration time is too long, confirm its parameters.  When overvoltage stall protection is enabled,  Overvoltage stall protection is enabled, when DC bus voltage exceeds the overvoltage stall voltage (F07.07); output frequency remains unchanged. When DC bus voltage is lower than the set value of F07.07, output frequency drops continuously and therefore the deceleration time is prolonged. 366