sinee — 12.2 Physical Interface

EM500 Open-Loop Vector Control Inverter User Manual 12. MODBUS Communication Protocol 12.1 Application Scope 1. Applicable series: EM500 2. Applicable network: Support MODBUS-RTU protocol, with the single-master/multi-slave communication network of RS-485 bus. A+ A- Master A- A+ A+ A- Inverter A+ A- Inverter A+ A- Inverter 1# 2# 3# 12.2 Physical Interface RS-485 asynchronous half-duplex communication mode is with the least significant bit given the priority for transmittance. RS-485 network address: 1 – 247 available for setting, 0 is the broadcast address. and 1-8-O-2, optional). RS-485 terminal default data format:

1-8-N-1 [2] (1-8-E-1, 1-8-O-1, 1-8-N-2, 1-8-E-2 Default bit rate of RS-485 terminal: 9600 bps (4800 bps, 19200 bps, 38400 bps, 57600 bps and 115200 bps, optional); It’s recommended to use shielded twisted cable as communication cable so as to reduce impacts of external disturbance upon communication. [2] 1-8-N-1 , 1 start bit – 8 characters per byte data – nonparity 1 – 1 stop bit. E, even parity; o, odd parity. 381