EM500 Open-Loop Vector Control Inverter User Manual 12.3.5 Data Frame Length The number of read/write registers for PDU of RTU frame of MODBUS message falls into the scope between 1 and 16. As for different function codes, the actual lengths of RTU frames are different. See Table 12-3 for details.
Table 12-3 RTU Length and Function Codes 397 7225H Reference Frequency 7228H Total Time of power on 7230H Warning Number others - 73FFH Not Used 7500H Performance Software Serial Number 1 Correspond to F12.22 7501H Performance Software Serial Number 2 Correspond to F12.23 7502H Function Software Serial Number 1 Correspond to F12.24 Product 7503H Function Software Serial Number 2 Correspond to F12.25 Informat ion 7504H Keypad Software Serial Number 1 Correspond to F12.26 7500H - 7505H Keypad Software Serial Number 2 Correspond to F12.27 75FFH 7506H Product Serial Number 1 Correspond to F12.28 7507H Product Serial Number 2 Correspond to F12.29 7508H Product Serial Number 3 Correspond to F12.30 7509H - 75FFH Not Used Other Not Used RTU frame length (byte) Maximum Function Code Normal Normal Abnormal Length(Byte) response response response 03 8 5+2Nr[4] 5 37 41 (06) 8 8 5 8 08 8 8 5 8 42 (10) 9+2N [5] w 8 5 41