sinee — 13.3.2.2 Write register or command function code, (0x400 ,no save EEPROM)

EM500 Open-Loop Vector Control Inverter User Manual 13.3.2.2 Write register or command function code, (0x400 ,no save EEPROM) The function code is used to write the non-holding register. The request message is the address and value to be written to the register. The normal status response message is the slave address + exception code. The function code can write up to two registers at a time.  request message  Response message  Error message The following is an example of a device operating at address 1 running at a frequency of 100% (7001H) forward running (7000H):

416 Register 08 Register 00 address values Lo Lo Register 00 values Hi Register 00 values Lo CAN-ID 0x400+slave address DLC(Date Length) 4*N Data Field N*4 Bytes CAN-ID 0x400+ Host address DLC(Date Length) 2 Data Field Slave address+ Abnormal code(00) CAN-ID 0x480+ Host address DLC(Date Length) 2 Data Field Slave address+ Abnormal code request Response Domain Domain Domain (hexadecimal (hexadeci (hexadecimal Name Name Name ) mal) ) (normal) (Abnorma