EM500 Open-Loop Vector Control Inverter User Manual 78 of Synthetic Frequency Auxiliary Channels 1: AI1 * Synthetic Frequency of Main and Auxiliary Channels 2: AI2 * Synthetic Frequency of Main and Auxiliary Channels 3: AI3 * Synthetic Frequency of Main and Auxiliary Channels 4: AI4 * Synthetic Frequency of Main and Auxiliary Channels 5:
High-Frequency Pulse (PULSE) * Synthetic Frequency of Main and Auxiliary Channels F00.14 Acceleration Time 1 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F00.15 Deceleration Time 1 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F00.16 Maximum Frequency 1.00 - 600.00 Hz 50.00 〇 F00.17 Upper Limit Frequency Control Options 0: Set through F00.18 1: AI1 2: AI2 3: AI3 4: AI4 (Expansion Card) 5: High-Frequency Pulse Input (X7) 6: Upper Limit Frequency Communication Percentage Setting 7:
Upper Limit Frequency Communication Direct Setting 0 〇 F00.18 Upper Limit Frequency Lower Limit Frequency F00.19 - Maximum Frequency F00.16 Hz 50.00 ● F00.19 Lower Limit Frequency 0.00 - Upper Limit Frequency F00.18 Hz 0.00 ● F00.20 Running Direction 0: Same 1: Opposite 0 ● F00.21 Reverse Control 0: Permit Forward/Reverse 1: Prohibit Reverse 0 〇 F00.22 F/R Deadband Time 0.00 - 650.00 s 0.00 ● F00.23 Carrier Frequency 1.0 - 16.0 (inverter rated power 0,75 – kHz 4.0 ●