sinee — 6.2 Function Parameter Table

EM600 High-Performance Vector Control Inverter User Manual 102 Function Name of Function Parameter Description Unit Default Property Code Code Integral Time Constant ACR-T2 0.000: No Integral F14.52 Not Used - - - - F14.53 SVC Zero Frequency Processing Method 0: Brake 1: Normal 2: No output 2 〇 F14.54 SVC Zero Frequency Band-Type Brake Current 50.0 - 400.0 (100.0=Idling Current) % 100.0 〇 F14.55 Not Used - - - - F14.56 Voltage Feedforward Gain 0 - 100 % 0 ● F14.57 Field Weakening Control Options 0: Disabled 1:

Direct Calculation 2; Automatic Adjustment 1 〇 F14.58 Field Weakening Voltage 70.00 - 200.00 % 95.00 ● F14.59 Maximum Field Weakening Current of Synchronous Motor 0.0 - 150.0 (100.0= Motor Rated Current) % 50.0 ● F14.60 Proportional Gain of Field Weakening Regulator 0.00 - 10.00 0.50 ● F14.61 Integral Time of Field Weakening Regulator 0.01 - 60.00 s 2.00 ● F14.62 MTPA Control Options of Synchronous Motor 0: Disabled 1:

Enabled 0 〇 F14.63 Gain of Autotuning at Initial Position 0 - 600 % 80 ● F14.64 Injection Current at Frequency of Low Frequency Range 0.00 - 100.00 (100.00= Motor Rated Frequency) % 10.00 ● F14.65 Injection Current at Low Frequency Range 0.0 - 60.0 (100.0= Motor Rated Current) % 20.0 ● F14.66 Low Frequency Range Regulator Gain of Injection Current 0.00 - 10.00 0.50 ● F14.67 Integral Time of Low 0.00 - 300.00 ms 10.00 ●