EM600 High-Performance Vector Control Inverter User Manual 12 MODBUS Communication Protocol 12.1 Application Scope 1. Applicable series: EM600 2. Applicable network: Support MODBUS-RTU protocol, with single-master/multi-slave communication network of RS-485 bus. Maste A+ A- r A- A+ A+ A- EM600 n# 12.2 Physical Interface RS-485 asynchronous half-duplex communication mode is with least significant bit given the priority for transmittance. RS-485 network address: 1 – 247 available for setting, 0 is broadcast address. RS-485 terminal default data format: 1-8-N-1 [2] (1-8-E-1, 1-8-O-1, 1-8-N-2, 1-8-E-2 and 1-8-O-2, optional). Default bit rate of RS-485 terminal:
9600 bps (4800 bps, 19200 bps, 38400 bps, 57600 bps and 115200 bps, optional); It’s recommended to use shielded twisted cable as communication cable so as to reduce impacts of external disturbance upon communication. [2] 1-8-N-1, 1 start bit – 8 characters per byte data – nonparity – 1 stop bit. E, even parity; o, odd parity. 12.3 Protocol Format 12.3.1 Message Format As shown in Figure 12-1, a standard MODBUS message includes start mark, RTU message (Remote Terminal Unit) and end mark.
RTU message PDU Start block of frame Stop block of frame =3.5 characters =3.5 characters Figure 12-1 RTU Message Frame 252 A- A+ EM600 1# A- A+ EM600 2# Address Function code Data CRC Parity 8 bits 8 bits N*8bits 2*8bits egister ddress Number of Registers Register content 2*8 bits 2*8bits 2*Number of Registers*8 bits