sinee — 12.3.3.1 Function Code 0x03 Read Multiple Registers or Status Bytes

EM600 High-Performance Vector Control Inverter User Manual 12.3.3.1 Function Code 0x03 Read Multiple Registers or Status Bytes In remote device, inverter uses this function code to read content of continuous blocks of holding register. Request PDU indicates start register address and number of registers. Divide register data of response message into two bytes for each register. For each register, the first byte includes high bit, the second byte includes low bit.  Request PDU  Response PDU N*=Number of Registers  Incorrect PDU The following is an example of requesting to read registers F19.00 - F19.05 (relevant information about last fault):

254 Function Code 1 byte 0x03 Initial Address 2 bytes 0x0000 - 0xFFFF Number of 2 bytes 1 - 16 Registers Function Code 1 byte 0x03 Number of Bytes 1 byte 2×N* Register Value N*×2 bytes Error Code 1 byte 0x83 Exception Code 1 byte 01, 02, 03 or 04 Request Response Field Name (0x) Field Name (normal) (0x) Field Name (0x) (abnormal) Function Code 03 Function Code 03 Function 83 Initial Address Hi 13 Number of Bytes 0C 03 (Example, the same below) Exception Initial Address 00 (F19.00)Register Value 00 Code Lo Hi (F19.00) Number of 00 Register Value Lo 11 Registers Hi (F19.00) Number of 06 Register Value Hi 00 Registers Lo (F19.01) Register Value Lo 00 (F19.01) Register Value Hi 00 (F19.02) Register Value Lo 00 (F19.02) Register Value Hi 01 (F19.03) Register Value Lo 2C (F19.03) Register Value Hi 00 (F19.04) Register Value Lo 00