EM600 High-Performance Vector Control Inverter User Manual 12.3.3.3 Function Code 0x42 Write Multiple Registers or Commands (Not to Save) This function code is used to write continuous non-holding register blocks (1 to 16 registers) in a remote device. Value requested for writing is described in request data field. Each register divides data into two bytes. Normal response shall return function, initial address and number of registers written. Request PDU N*=Number of Registers Response PDU Incorrect PDU The following is an example of a request for setting acceleration time 1 (F00.14) as 5.00 and deceleration time 1 (F00.15) as 6.00:
256 Function Code 1 byte 0x42 Initial Address 2 bytes 0x0000 - 0xFFFF Number of 1 byte 1 - 16 Registers Number of Bytes 1 byte 2×N* Register Value N*×2 bytes Function Code 1 byte 0x42 Initial Address 1 byte 0x0000 - 0xFFFF Number of 1 byte 1 - 16 Registers Error Code 1 byte 0xC2 Exception Code 1 byte See Table 12–4 Request Response Field Name Field Name Field Name (0x) (0x) (0x) (normal) (abnormal) Function 42 Function 42 Function C2 Initial Address Hi 00 Initial Address Hi 00 03 Exception 0E Initial Address 0E Initial Address Lo Code Lo 00 Number of 00 Number of Registers Hi Registers Hi 02 Number of 02 Number of Registers Lo Registers Lo Number of Bytes 04 Register Value Hi 01 (F00.14) Register Value Lo F4 (F00.14) Register Value Hi 02 (F00.15) Register Value Lo 58 (F00.15)