EM600 High-Performance Vector Control Inverter User Manual 262 Address Space Description Fault Information xxH Fault status of inverter, “xx” is the fault code. 7201H Status word 2 Bit0 Set Direction 1 -: Valid Setting 0 +: Valid Setting Bit1 Running Direction 1 Frequency Output, Reverse 0 Frequency Output, Forward Bit 3 - 2 Control Mode 00 Speed Control Mode 01 Torque Control Mode 10 Servo Control Mode 11 Not Used Bit4 Parameter Protection 1 Enabled 0 Disabled Bit 6 - 5 Not Used Bit 8 - 7 Set Mode 00 Keypad Control 01 Terminal Control 10 Communication Control 11 Not used Bit9 Not Used Bit15 - 10 Not Used 7202H Monitoring frequency +/- status word 1 (1: -; 0:

+) Bit0 Output Frequency Bit1 Input Frequency Bit2 Synchronous frequency Bit3 PG Feedback Frequency Bit4 Estimated Feedback Frequency Bit5 Estimated Slip Frequency Bit6 Load Speed Bit 15 - 7 Not Used 7203H Output Frequency 7204H Output Voltage 7205H Output Power 7206H Running Speed 7207H Bus Voltage 7208H Output Torque 7209H Switch Quantity Input 1 15 14 13 12 11 10 9 8 * * * * * X11 X10 X9 7 6 5 4 3 2 1 0 X8 X7 X6 X5 X4 X3 X2 X1 720AH Switch Quantity Input 2 15 14 13 12 11 10 9 8 VX8 VX7 VX6 VX5 VX4 VX3 VX2 VX1 7 6 5 4 3 2 1 0 * * * * AI4 AI3 AI2 AI1 720BH Switch Quantity 15 14 13 12 11 10 9 8 * * * * * * * *