sinee — 13.2 Power on

EM600 High-Performance Vector Control Inverter User Manual 13 660V inverter Commisioning Instructions 13.1 Wiring R/S/T is connected with grid input 660VAC. U/V/W is connected with motor. PE is connected with grid PE. Only external brake unit is applied for 660V inverter. Details refer to the diagram below. Please check the input power cables, motor power cables and brake unit power cables before power on. 制动电阻(选配件) Braking resistor (optional) 制动单元(选配件 ) Braking unit (optional) R S U V T W M Figure 13-1 660V inverter wiring diagram 13.2 Power on After checking wiring is correct and the inverter is power-on motor parameters (F01 group) should be set properly.

The motor parameters must be according to the parameters on the motor nameplate. After setting inverter starts stationary and rotational autotuning, respectively for asynchronous motor. The difference between default parameters for 660V inverter and chapter 6 function code default values is shown as below. F04.01 Start Frequency 0.75Hz F04.02 Start Frequency Retention time 2 F04.06 Pre-Excitation Current 200.0% F04.07 Pre-Excitation 1.00s F05.10 V/F Rotor Voltage Drop Compensation Gain 0.0% 273