sinee — IV.2 Installation Instructions

EM600 High-Performance Vector Control Inverter User Manual Appendix IV CANopen Expansion Card (EC-CM-C1) IV.1 General Communication card EC-CM-P1 is defined as CANOPEN slave communication card and used to connect EM600 inverter to CANOPEN network. Main features:  It supports Node Guard protocol and master can use this function to view device status.  It supports Heartbeat protocol, with which slave reports present status to master regularly.  It supports NMT network management protocol, with which inverter receives message for inverter status control by master and changes its own communication status.

 SDO only supports accelerated sending mechanism, up to 4 bytes in transmission, and can be used to read and write device parameters.  PDO supports 4 groups and user may select 1 group randomly; this can be used to transmit the data required for real time transmission in transmission communication process, up to 4 bytes for each frame. IV.2 Installation Instructions  Install CANopen expansion card into expansion slot EC-B (make sure it is installed and buckled properly).  Disassemble or install CANopen expansion card only after inverter is powered off.

Figure 3 CANopen Expansion Card Installation Point CANopen expansion card at interface and location hole of expansion slot, and fix them with screws. 286