EM600 High-Performance Vector Control Inverter User Manual Table 18 DIP Switch of DeviceNet Expansion Card 290 Indicator LED Status Display Solution Master Established Red Lamp Flicker Communication Card Already Connected Online and Single I/O Communication Overtime 1. Configure communication card to master scan list 2. Re-download configuration data to master Red Lamp On MACID Detection Failure; No Network Power Supply Bus-off Bus-off 1. Confirm that there is no repeated node address on the network 2. Check if network power supply is normal 3.
Confirm whether communication rate and wiring are normal MS Off No Power Supply Check whether power of communication card works normally Green Lamp Flicker Wait for I/O Data Switch PLC to RUN status Green Lamp On Normal I/O Data No need to do anything Red Lamp Flicker Mapping Error Configure communication card or power on inverter again Red Lamp On Hardware Error Return for repairing US Off No Power Supply Check if power of communication card works normally Green Lamp Flicker Wait for Inverter to Return Data Confirm that communication card and inverter are connected together normally Green Lamp On Normal Data with Inverter No need to do anything Red Lamp Flicker Communication Overtime Confirm that communication card and inverter are connected together normally Red Lamp On Communication Failure Power it on again S2 S2 Function ON OFF S1 Select a matching end resistor