EM630/TC6A Closed-Loop Vector Hoist Inverter User Manual 3.2.6.9 Wiring Distance Between Inverter and Motor The longer the wiring distance between the inverter and the motor is, the higher the carrier frequency will be and the greater the high-frequency harmonic leakage current on its cables will be accordingly. As a result, an adverse impact may be produced upon the inverter and its devices nearby. Adjust the carrier frequency by reference to Table 3–3 to reduce the high-frequency leakage current.  If the motor wiring is over 50m, connect a 3-phase inverter output AC reactor of the same capacity to the terminals U, V and W of the inverter.

Table 3–3 Wiring Distance and Carrier Frequency Between the Inverter and the Motor 3.2.7 Main Circuit Cable and Terminal Screw Size Main circuit cable and terminal screw sizes are shown in Table 3–4. Table 3–4 Cable and Terminal Screw Specifications 37 Wiring Distance Between Inverter and Below 50m Below 100m Below 100m Motor Carrier Frequency Below 10 kHz Below 8 kHz Below 5 kHz F00.23 Function Code 10.0 8.0 5.0 Tightening Cable Terminal Model No.

Terminal Symbol Torque Size Cable Type Screw (N.m) (mm2) EM630-4R0-3B , ,R,S,T,U,V,W,PB, M3.5 1.2 - 1.5 4 750V Cable EM630-5R5-3B M4 1.5 - 2.0 6 EM630-7R5-3B EM630-011-3B R,S,T,PB, ,,U,V,W M5 3.0 - 4.0 10 EM630-015-3B EM630-018-3B EM630-022-3/3B R,S,T, ,,U,V,W, M6 4.0 - 5.0 16 EM630-030-3/3B 25 EM630-037-3/3B M8 9.0 - 10.0 25 EM630-045-3B M8 9.0 - 10.0 35 EM630-055-3B ,R,S,T,PB, ,U,V,W, M10 17.0 - 22.0 35 EM630-075-3B 60 EM630-045-3 M8 9.0 - 10.0 35 EM630-055-3 ,R,S,T, , ,U,V,W, M10 17.0 - 22.0 35 EM630-075-3 60