sinee — 9.2 Table of functional parameters

User Guide of EM730 Series Inverter 105 F27.01 Feedforward gain action channel 0: feedforward gain * set source B 1: Feedforward gain * set source A 2: Feedforward gain * 10V 1 〇 F27.02 Feedforward gain input mode 0: No change in feedforward gain 1: 0.00 to upper limit of feedforward gain 2: - upper limit of feedforward gain to + upper limit of feedforward gain 1 〇 F27.03 Feedforward control Ones place: Feedforward reset option 0: Automatic reset 1: Terminal reset Tens place: Feedforward power-off stop option 0: Save after power failure 1: Not save after power failure Hundreds place: Options of continuous feedforward calculation 0: Not calculate 1:

Calculate 10 〇 F27.04 Upper limit of feedforward gain 0.00~500.00 % 500.00 〇 F27.05 Initial feedforward gain 0.00~500.00 % 50.00 ● F27.06 Feedforward gain filter time 0~1000 ms 0 ● F27.07 Feedforward range 0 0.00 to feedforward range 1 % 4.00 ● F27.08 Feedforward range 1 Feedforward range 0 to feedforward range 2 % 12.00 ● F27.09 Feedforward range 2 Feedforward range 1 to feedforward range 3 % 23.00 ● F27.10 Feedforward range 3 Feedforward range 2 to feedforward range 4 % 37.00 ● F27.11 Feedforward range 4 Feedforward range 3 to feedforward range 5 % 52.00 ● F27.12 Feedforward range 5 Feedforward range 4 to 100.00 % 72.00 ● F27.13 Soft start increment 0.00 - 50.00 %/S 0.60 ● F27.14 Feedforward increment 1 0.00 - 50.00 %/S 0.11 ● F27.15 Feedforward increment 2 0.00 - 50.00 %/S 0.30 ●