User Guide of EM730 Series Inverter 23 supply the maximum output current of 100mA. COM Power grounding terminal Power grounding terminal of the external power supply, and common side of the digital input terminal 10V Analog terminal power supply Supply 10V power to external devices. Maximum output current: 10.5±0.5V/20mA, usually as the power supply of the external potentiometer GND Analog power grounding terminal Grounding terminal of analog input and output Analog input AI1 Analog voltage input -10V to 10V, 50kΩ input impedance, bipolar analog voltage input AI2 Analog current/voltage input Current or voltage type Input range:
0/4-20mA or 0-10V M1 Analog voltage/current output 0-10V/0-20mA; output accuracy: ±2% Analog output X1 Multi-function input terminal Program the corresponding terminals by setting function codes, to realize the input control of the set functions. The input terminal supports PNP and NPN input modes, and the default mode is the NPN input mode. X5 can also be used as the high-frequency pulse input, with the input frequency up to 100kHz. X2 X3 X4 Digital input X5 port Y1 Open collector output terminal It can be programmed as the multi-function output terminal. Multi-function digital output YCM Common side of Y The common side YCM of Y terminal and the