User Manual of EM730/EM730E Series Inverter Xi input Close Off Positive logic sampling Valid Invalid Negative logic sampling Invalid Valid Fig. 7-12 Schematic Diagram of Positive/Negative Logic Sampling of Terminal When the bit is set to 0, the multi-function input terminal is valid in the closed status and invalid in the open status; When the bit is set to 1, the multi-function input terminal is valid in the open status and invalid in the closed status. to 0 or 1. Take F02.15 as an example, as shown in the following table: These function code are subject to bit operation. You only need to set the corresponding bit Table 7-7 Function Code Details of Bit Operation anything.
The seventh bit is reserved and cannot be set. The specific displayed value does not mean For example: To set the terminal X1 to reverse logic, you only need to set the 0 th bit corresponding to X1 to 1, i.e. F02.15=xxx xxxx1. corresponding to X1 and 4 th bit corresponding to X5 to 1. That is, 02.15=xxx 1xxx1. To set the terminals X1 and X5 to reverse logic, you only need to set the 0 th bit ★ This function is for logic matching with other external devices.
160 Setting item * * * X5 X4 X3 X2 X1 Corresponding bit * * * 4 3 2 1 0 Settings * * * 0/1 0/1 0/1 0/1 0/1 Default Function code Function code name Parameter description Unit Attribute setting F02.17 Filtering times of digital input terminal 0-100; 0: no filtering; n: sampling once in n ms 2 〇