User Manual of EM730/EM730E Series Inverter If the free stop terminal has been set and enabled, the inverter will be immediately in the free stop status. Even if this terminal is disabled, the inverter will not restart running. Instead, the running command must be entered again to start the inverter. frequency is less than the set frequency during deceleration stop, and the time of DC braking for F04.20 : Set the starting frequency of DC braking in deceleration to stop. Once the output stop is not 0, DC braking for stop will be enabled. F04.21 : Set different values to apply the torques of DC braking for stop. be invalid.

When an external terminal sends a signal of DC braking for stop, the duration of DC F04.22 : Set the duration of DC braking for stop. If F04.22=0.00, DC braking for stop will braking for stop will be larger of the valid time of the signal of DC braking for stop from the external terminal and the set time of F04.22. F04.23 : When the output frequency reaches the set value of F04.20 during deceleration to stop, and the set time of F04.23 is up, DC braking will be enabled. The process of DC braking for stop is shown in Fig. 7-.

183 Function Default Function code name Parameter description Unit Attribute code setting F04.20 Starting frequency of DC braking in stop 0.00 to maximum frequency F00.16 Hz 0.00 〇 F04.21 DC braking current in stop 0.0 to 150.0 (100.0 = rated current of motor) % 100.0 〇 F04.22 DC braking time in stop 0.00~30.00 0.00: invalid s 0.00 〇 F04.23 Demagnetization time for DC braking in stop 0.00 - 30.00 s 0.50 〇