User Manual of EM730/EM730E Series Inverter inverter should decrease for PID balance. Take the water supply control as an example. When the pressure increases, the pressure feedback will increase. The output frequency of the inverter must be decreased to reduce the pressure and keep the constant pressure. In this case, the PID should be set to the positive action.  When the feedback signal is greater than the PID setting, the output frequency of the inverter needs to increase for PID balance. Take temperature control as an example. The PID regulator needs to be set to negative action to control the temperature. process PID module.

Switching or linear interpolation of the two sets of parameters can be For a variety of complex scenes, two sets of PID parameters have been introduced into the performed according to the function setting (F09.11) and input conditions [e.g. input function “43: PID parameter switching”, and deviation e(k)). See the instruction Table 7-15 for details. 221 Function Default Function code name Parameter description Unit Attribute code setting F09.05 Proportional gain 1 0.00-100.00 0.40 ● F09.06 Integral time 1 0.000 to 30.000; 0.000: no integral s 2.000 ● F09.07 Differential time 1 0.000-30.000 ms 0.000 ● F09.08 Proportional gain 2 0.00-100.00 0.40 ● F09.09 Integral time 2 0.000 to 30.000; 0.000:

no integral s 2.000 ● F09.10 Differential time 2 0.000-30.000 ms 0.000 ● F09.11 PID parameter switching conditions 0: no switching 1: switching via digital input terminal 2: automatic switching according to deviation 3: Automatic switching by frequency 0 ● F09.12 PID parameter switching deviation 1 0.00 - F09.13 % 20.00 ● F09.13 PID parameter switching deviation 2 F09.12 - 100.00 % 80.00 ●