User Manual of EM730/EM730E Series Inverter PID parameters Parameter 2 Parameter 1 | Deviation | 100.00% 0 Switching deviation 1 Switching deviation 2 Fig. 9-28 Schematic Diagram of Automatic Switching of PID Parameters based on Deviation (F19.11=2) The inverter starts running, and the process PID module constantly outputs the initial PID value (F09.14) for the initial PID holding time (F09.15). Then the output is adjusted by the PID based on the deviation. Specific effects are shown in Fig. 9-29. When the initial PID holding time is set to 0.00s, i.e. F09.15=0.00, the initial PID output function will be invalid.

223 Function Default Function code name Parameter description Unit Attribute code setting F09.14 Initial PID value 0.00-100.00 % 0.00 ● F09.15 PID initial value holding time 0.00~650.00 s 0.00 ●