sinee — EM730 User Manual

User Manual of EM730/EM730E Series Inverter t t wait 2 t wait 3 t send t wait 1 t return Fig. 7-31 Timing Parse Diagram of Complete Data Frame The EM730/EM730E series inverter supports the master-slave communication function. That is, one inverter works as the host and others as slaves. The slaves work according to the command sent by the host, so that these inverters can work synchronously.  The inverter used as the host is set as follows: F10.05=1: enable the master-slave communication function; F10.06=1 or 2: select the current inverter as the host (only one inverter can be set as the host in a network); F10.07:

select the variable to be synchronized, such as the output current (set F10.07=5).  The inverter is used as the slave is set as follows: 234 Function Default Function code name Parameter description Unit Attribute code setting F10.05 Options of master-slave communication function 0: Invalid 1: valid 0 〇 F10.06 Master-slave options 0: slave 1: host (Modbus protocol broadcast transmission) 0 〇 F10.07 Data sent by host 0: output frequency 1: set frequency 2: output torque 3: set torque 4: PID setting 5: output current 1 〇 F10.08 Proportional factor of slave reception 0.00-10.00 (multiple) 1.00 ● F10.09 Host sending interval 0.000-30.000 s 0.200 ●