User Manual of EM730/EM730E Series Inverter Output frequency Set frequency + width Set frequency - Set frequency width 0 Time Output terminal Invalid 0 Time Fig. 7-36 Schematic Diagram of FAR Detection up to output frequency (FAR)”, and the absolute value of the difference between the |output As shown in Fig. 7-36, when the multi-function output terminal or relay output is set to “2: frequency| and |given frequency| is less than or equal to the set value of FAR detection width (F15.20) during inverter operation, the corresponding function terminal will output the active level. Otherwise, this terminal will output the inactive level.
259 Invalid Valid Valid Function Default Function code name Parameter description Unit Attribute code setting F15.21 Output frequency detection FDT1 0.00 to maximum frequency F00.16 Hz 30.00 〇 F15.22 FDT1 hysteresis -(Fmax-F15.21)~F15.21 Hz 2.00 〇 F15.23 Output frequency detection FDT2 0.00 to maximum frequency F00.16 Hz 20.00 〇 F15.24 FDT2 hysteresis -(Fmax-F15.23)~F15.23 Hz 2.00 〇