User Manual of EM730/EM730E Series Inverter of (output frequency detection, output frequency detection - hysteresis,), the output level of the corresponding function terminal will remain unchanged. current selected F15.25 channel, and also perform internal operation and external alarm The analog level detection function is used to detect and monitor the analog input of the monitoring. Two detection conditions can be set, but only one analog input channel can be detected. Analog AI % Detection level Hysteresis Output 0 Time (s) terminal 0 Invalid Invalid Valid Fig. 7-38 Schematic Diagram of ADT Detection Time (s) As shown in Fig.

7-38, a valid starting point has been set for the detection level. When the percentage of analog input is above the detection level after offset processing, the ADT function will be valid. The conditions for invalid ADT function are dependent on the one-way downward hysteresis.

When the conversion result of analog input decreases to less than the result of 261 Function Default Function code name Parameter description Unit Attribute code setting F15.25 Options of analog level detection ADT 0:AI1 1:AI2 0 ○ F15.26 Analog level detection ADT1 0.00-100.00 % 20.00 ● F15.27 ADT1 hysteresis 0.00 to F15.26 (valid down in one direction) % 5.00 ● F15.28 Analog level detection ADT2 0.00-100.00 % 50.00 ● F15.29 ADT2 hysteresis 0.00 to F15.28 (valid down in one direction) % 5.00 ●