User Manual of EM730/EM730E Series Inverter Ones place of F27.20 = 0: automatic detection Wire disconnection is detected automatically by the inverter. In this mode, F09.35 and F09.36 must be set accurately. Ones place of F27.20 = 1: external signal Wire disconnection is detected by the external proximity switch. Tens place of F27.20 = 0: Detection with the output greater than the lower limit of material cutoff detection When the stop command is received, and the output frequency is less than the set value of F27.22, wire disconnection will not be detected. Tens place of F27.20 = 1: no detection Wire disconnection will not be detected. Hundreds place of F27.20 = 0:
Protection terminal action only In case of wire disconnection, the inverter will continue to run at the set frequency of F27.24, and only the 68# function terminal and protection output terminal will act. 295 1: External signal Tens place: Material cutoff detection control 0: Detect when the output is greater than the lower limit of material cutoff detection 1: no detection Hundreds place: Material cutoff handling mode 0: Protection of terminal action only 1: Delayed stop and protection report 2: Material cutoff protection 3: Automatic reset of material cutoff protection 4: Material cutoff detection terminal output only 5:
Automatic reset of material cutoff detection terminal Thousands place: Brake mode 0: mode 0 1: mode 1 Myriabit: Reverse unwinding mode 0: No speed limit 1: Reverse speed limit by F27.24