User Manual of EM730/EM730E Series Inverter RTU message PDU Start End ≥3.5 characters ≥3.5 characters Fig. 12-20 Schematic Diagram of Message Frame in RTU Mode The RTU message includes the address code, PDU (Protocol Data Unit) and CRC[3 ] check. The PDU includes the function code and data part (mainly including the register address, number of registers, register content and the like; the detailed definitions of function codes are different, as shown in 11.3.3Function code ). [3]: the low byte of CRC check is in front of the high byte. 11.3.2 Address code 11.3.3 Function code The classification of MODBUS function codes is shown in Fig. 12-21.
127 ( 0x7F ) Common function code 110 ( 0x6E ) 100 ( 0x64 ) User-defined function code Common function code 72 ( 0x48 ) User-defined function code 65 ( 0x41 ) Common function code 1 ( 0x1 ) Fig. 12-21 Classification of MODBUS Function Codes 318 Address Function code Data CRC check 8 digits 8 digits N*8 bits 2*8 bit Address of register Number of registers Register content 2*8 bit 2*8 bit 2 * number of registers * 8 bits Address Range Purpose 1 - 247 Slave 0 Broadcast