User Manual of EM730/EM730E Series Inverter ★ The function code 0x10 cannot be used if modified frequently, in order to avoid damage to the inverter, as detailed in 1.1.1.5.
11.3.4 Register address distribution Table 12-31 Detailed Definition of Register Address of MODBUS Protocol 328 Starting address Lo 00 Starting address 00 Lo Number (Hi) of registers 00 Number (Hi) of 00 registers Number (Lo) of registers 02 Number (Lo) of 02 registers Number of bytes 04 Register value Hi 00 (F03.00) Register value Lo 01 (F03.00) Register value Hi 00 (F03.01) Register value Lo 03 (F03.01) Address Space Note For the function code FXX.YY, the high order is hexadecimal of XX and the low order is hexadecimal of YY. For example, the address of F00.14 is 000EH (00D=00H, 14D=0EH).
Function code 0000H - 6F63H When the parameters are set with the function code 0x06 or 0x10, the function that “the settings are valid immediately and not saved after power-down” can be realized in the form of “original address +8000H”. For example, the corresponding address of F00.14 is 800EH (=000EH+8000H). Function code (not saved after power-down) 8000H-EF63H 7000H control word 0000H Invalid command 0001H Forward running Control 0002H Reverse running comman 0003H JOG forward d (write 0004H JOG reverse only) 0005H Deceleration to stop 7000H 0006H Stop the controller quickly ~ 0007H Free stop 71FFH 0008H Reset protection 0009H +/- input switching 000BH JOG stop