sinee — EM730 User Manual (EN)

User Manual of EM730/EM730E Series Inverter Table 3-1 Cable Dimensions and Terminal Screw Specifications Note: 1: The specifications of the wire are dependent on its voltage drop. Under normal circumstances, the voltage drop calculated by the following formula should be less than 5V. Voltage drop = 3 * wire resistivity (Ω/KM) * wire length (m) * rated current (A) * 10 -3 2: If the wire is in a plastic slot, it should be enlarged by one level. 3: The wire should be crimped to the round terminal suitable for the wire and terminal screw. 4: The specification of the ground wire should be the same as that of the power cable smaller than 16mm 2 .

When the power cable is 16mm 2 or larger, the ground wire should not be smaller than 1/2 of the power cable. 3.2.7 Ground wire  The ground terminal must be grounded.  Pay special attention to the third type of grounding (grounding resistance: less than  The ground wire must not be shared by the welding machine and power devices. 10Ω).  Select the ground wire according to the technical specifications for electrical equipment, and minimize the length of the ground wire connected to the grounding  Where two or more inverters are used, the ground wires must not form a loop. The point. correct and incorrect grounding methods are shown in Table 3-10.

Inverter Inverter Inverter Inverter Inverter Inverter Fig.3-10 Connection of Ground Wire 38 EM730/EM730E-090-3 M10 17.0~22.0 60 EM730/EM730E-110-3 90 EM730/EM730E-132-3 R, S, T, P, +, -, U, V, W 90 EM730/EM730E-160-3 120