User Manual of EM730/EM730E Series Inverter RS485 communication interface of host + terminal - terminal GND A+ GND A- A+ GND A- A- A+ GND A- A+ GND ON Inverter S1 OFF Inverter S1 OFF Inverter S1 OFF Inverter S1 Fig. 3-17 Wiring of Communication Terminals of Multiple Inverters  Connection to the host via RS485/RS232 adapter for communication: Inverter A+ RS232 communicatio A- RS485/RS232 adapter n interface of S1 ON GND host Fig.

3-18 Communication Terminal Wiring 3.3.8 Wire and screw dimensions of control circuit  In order to reduce the interference and attenuation of the control signal, the control signal connection cable should be less than 50 m long, and the distance between the control signal connection cable and power line should be greater than 30 cm. Use the twisted-pair shielded cable when analog signals are externally inputted.  It is recommended to use the wire with a diameter of 0.5-1 mm 2 in the control circuit.  The terminal block of the EM730/EM730E series inverter is composed of through-type control circuit terminals. Install it with the PH0 Phillips screwdriver.

The tightening torque should be 0.5N.m. 3.3.9 Precautions for control circuit wiring  Connect the control circuit connection wires and other wires separately.  Connect the control circuit terminals EA, EB, EC, and Y1 separately from other control circuit terminals.  In order to avoid malfunction caused by interference, use the twisted shielded cables 45