User Manual of EM730/EM730E Series Inverter 71 F02.00 Options of X1 digital input function 0: no function 1: terminal running (RUN) 2: running direction (F/R) 3: stop control in three-line operation 4: forward jog (FJOG) 5: reverse jog (RJOG) 6: terminal UP 7: terminal DOWN 8: clear UP/DOWN offset 9: free stop 10: Reset protection 11: multi-segment speed terminal 1 12: multi-segment speed terminal 2 13: multi-segment speed terminal 3 14: multi-segment speed terminal 4 15: multi-segment PID terminal 1 16: multi-segment PID terminal 2 17: multi-segment torque terminal 1 18: multi-segment torque terminal 2 19: acceleration and deceleration time terminal 1 20:
acceleration and deceleration time terminal 2 21: Acceleration and deceleration prohibition 22: operation pause 23: External protection input 24: Switching of RUN command to keyboard 25: switching of RUN command to communication 26: Frequency source switching 27: clearing of regular running time 28: speed control/torque control switching 29: torque control prohibition 30: motor 1/motor 2 switching 31: resetting of simple PLC status (running from the first segment, with the running time cleared) 32: simple PLC time pause (keep running at current segment) 33: retention 34: counter input (≤250Hz) 35: high-speed count input (≤100kHz, only valid for X5) 36: count clearing 37:
length counter input (≤250Hz) 38: High-speed length counting input (≤100kHz, only valid for X5) 39: Reset length (clear by meter) 40: Pulse input (≤100kHz, only valid for X5) 1 〇 F02.01 Options of X2 digital input function 2 〇 F02.02 Options of X3 digital input function 11 〇 F02.03 Options of X4 digital input function 12 〇 F02.04 Options of X5 digital input function 13 〇 F02.07 Options of AI1 digital input function 0 〇 F02.08 Options of AI2 digital input function 0 〇